How to improve heat exchange efficiency of plate heat exchanger & reduce thermal resistance

Frist Improve heat transfer efficiency
Plate heat exchanger is a wall heat transfer heat exchanger, the cold fluid heat transfer through the heat exchanger plate, the fluid is in direct contact with the plate, the heat transfer mode is heat conduction and convection heat transfer. The key to improving the heat transfer efficiency of plate heat exchangers is to increase the heat transfer coefficient and the logarithmic mean temperature difference.
(1) increase heat transfer coefficient of heat exchanger
Only improve the surface thermal coefficient on both sides of the plate cold and hot, reduce the thermal resistance of the scale layer, select the plate with high thermal conductivity, reduce the thickness of the plate, can effectively improve the heat transfer Heat transfer coefficient of the device.
1 increase the surface heat transfer coefficient of the plate
Because the corrugated plate heat exchanger can cause turbulence of fluid at a small flow rate, it can obtain a high surface heat transfer coefficient, surface heat transfer coefficient and the geometry of the plate corrugation The flow state of the medium is related. The waveform of the plate includes a herringbone shape, a straight shape, a spherical shape, and the like. After years of research and experiments, it is found that the herringbone plate with triangular shape of corrugation has a high surface heat transfer coefficient, and the larger the angle of the corrugation, the higher the medium flow velocity in the flow channel between the plates, the greater the surface heat transfer coefficient. .
2 reduce the thermal resistance of the fouling layer
The key to reducing the thermal resistance of the fouling layer of the heat exchanger is to prevent the structure of the plate. When the thickness of the sheet structure is 1 mm, the heat transfer coefficient is reduced by about 10%. Therefore, it is necessary to pay attention to monitoring the water quality at both ends of the heat exchanger, preventing the structure of the plate and preventing the inclusion of impurities in the water on the plate. Some heating units add chemicals to the heating medium in order to prevent water theft and corrosion of steel parts. Therefore, it is necessary to pay attention to the water and viscous agents causing debris to contaminate the heat exchanger plates. If there is viscous debris in the water, it should be treated with a special filter. When using a drug, it is advisable to choose a non-stick agent.
3Select a plate with high thermal conductivity
Plate material can choose austenitic stainless steel, titanium alloy, steel alloy and so on. Stainless steel has good thermal conductivity, thermal conductivity of about 14.4W/(mk), high strength, good stamping performance, and is not easily oxidized. The price is lower than that of titanium alloy and copper alloy, but its resistance to chloride ion corrosion is poor.
4Reduce the thickness of the plate
The design thickness of the plate has nothing to do with its corrosion resistance, and is related to the pressure bearing capacity of the heat exchanger. The plate is thickened to improve the pressure bearing capacity of the heat exchanger. When the herringbone plate is used, the adjacent plates are inverted and the corrugations are in contact with each other, forming a dense and uniform distribution finger. The plate corner and edge sealing structure have been gradually improved, so that the heat exchanger has a good pressure. ability. Under the premise of satisfying the pressure bearing capacity of the heat exchanger, a smaller thickness of the plate should be selected as much as possible.
(2) Improve the logarithmic mean temperature difference
Plate heat exchanger flow patterns have countercurrent, downstream and mixed flow patterns. Under the same working conditions, the logarithmic mean temperature difference is large in the countercurrent, small in the downstream, and the mixed flow is in between. The method of increasing the logarithmic mean temperature difference of the heat exchanger is to adopt a mixed flow pattern of countercurrent or near countercurrent as much as possible, to increase the temperature of the hot side fluid as much as possible, and to reduce the temperature of the cold side fluid.
(3) Determination of the location of the inlet and outlet pipes
For a single-flow plate heat exchanger, for the convenience of maintenance, the fluid inlet and outlet pipes should be placed on the fixed end side of the heat exchanger as much as possible. The greater the temperature difference of the medium, the stronger the natural convection of the fluid, and the more obvious the influence of the formed retention zone. Therefore, the inlet and outlet of the medium should be moved in and out according to the hot fluid, and the cold fluid is placed in and out to reduce the influence of the retention zone. Improve heat transfer efficiency.
Second, method of reducing heat exchanger resistance
Increase the average flow rate of the medium in the flow channel between the plates, can improve the heat transfer coefficient and reduce the heat exchanger area. However, increasing the flow rate will increase the resistance of the heat exchanger, increase the power consumption of the circulating pump and the cost of the equipment, and it is uneconomical to obtain a slightly higher heat transfer coefficient by increasing the flow rate. When the flow rate of the hot and cold medium is relatively large, the following methods can be used to reduce the resistance of the heat exchanger and ensure a high heat transfer coefficient.
(1)Using a hot mixing plate
The plate of the hot mixing plate has the same corrugated geometry on both sides, and the plate is divided into a hard plate and a soft plate according to the angle of the herringbone corrugation, the angle is greater than 90 & deg; (generally 120 & deg; left and right) is hard Plate, the angle is less than 90 & deg; (generally 79 & deg; left and right) is a soft board. The surface of the hot-mixed plate has a high heat transfer coefficient, a large fluid resistance, and a soft plate. The hard board and the soft board are combined to form a flow path with high, medium and low characteristics to meet the requirements of different working conditions.
When the flow of hot and cold medium is relatively large, the use of a hot mixing plate can reduce the area of ??the plate compared to a heat exchanger with a symmetrical single process. The diameters of the corner holes on both sides of the hot and cold plates are generally equal. When the flow ratio of the hot and cold medium is too large, the pressure loss on the side of the cold medium is large. In addition, the hot mix plate design technology is difficult to achieve accurate matching, often resulting in limited plate area. Therefore, it is not advisable to use a hot mixing plate when the flow ratio of the hot and cold medium is too large.
(2) using asymmetric plate heat exchanger
Symmetrical plate heat exchanger consists of plates with the same corrugated geometry on both sides of the plate, forming a plate heat exchanger with the same cross-sectional area of ??the hot and cold runners. Asymmetric plate heat exchangers change the structure of the two sides of the plate according to the heat transfer characteristics and pressure drop requirements of the hot and cold fluids, forming a plate heat exchanger with different cross-sectional areas of hot and cold flow channels, and one side of the wide flow channel. The angular diameter is large. The heat transfer coefficient of the asymmetric plate heat exchanger is reduced slightly, and the pressure drop is greatly reduced. When the flow rate of the hot and cold medium is relatively large, the asymmetric single flow can reduce the plate area by 15% — 30% compared with the symmetric single flow heat exchanger.
(3)Multi-process combination
When the flow of hot and cold medium is large, multi-flow combination arrangement can be adopted, and more flow is adopted on the small flow side to increase the flow rate and obtain a higher heat transfer coefficient. A smaller flow is used on the side of the large flow to reduce heat exchanger resistance. The mixed flow pattern appears in the multi-flow combination, and the average heat transfer temperature difference is slightly lower. The fixed end plate and the movable end plate of the plate heat exchanger adopting the multi-process combination are taken over, and the workload is large during maintenance.
(4) Set the heat exchanger bypass pipe
When the flow rate of the hot and cold medium is relatively large, a bypass pipe can be arranged between the outlets of the heat exchanger on the large flow side to reduce the flow into the heat exchanger and reduce the resistance. For ease of adjustment, a regulating valve should be installed on the bypass pipe. The method should adopt a reverse flow arrangement to make the temperature of the cold medium heat exchanger higher, and ensure that the temperature of the cold medium after the heat exchanger outlet is merged can meet the design requirements. The heat exchanger bypass pipe can ensure the heat transfer coefficient of the heat exchanger and reduce the heat exchanger resistance, but the adjustment is slightly complicated.
(5) Choice of plate heat exchanger form
The average flow velocity of the medium in the flow path between the heat exchanger plates is preferably 0.3 & mdash; 0.6 m / s, and the resistance is preferably not more than 100 kPa. According to different flow ratios of cold and heat medium, different types of plate heat exchangers can be selected, and the cross-sectional area ratio of the asymmetric plate heat exchanger is 2. Heat exchanger bypass pipes can be used with symmetrical or asymmetrical, single-flow or multi-flow plate heat exchangers, but detailed thermal calculations should be performed.
2019/05/11 10:24:33 4751 Click

星闪电力应用破局,全球首个基于星闪的智能开关柜亮相CEIC2025 美国称在委内瑞拉封锁中拦截了第二艘油轮 张瑜:摆脱“超常规”,春水向“中游”——张瑜旬度会议纪要No.128 新华社评论员:树立和践行正确政绩观——十论学习贯彻中央经济工作会议精神 王张悦:养老特许信托可以满足委托人“人财安全”与“生活尊严”的诉求 周末影响市场重要资讯回顾:网信办、证监会严打资本市场谣言,摩尔线程发布新一代GPU架构,日本加息25基点 小马智行-W午前涨超9% 公司已在广州实现单车盈利|小马智行-W 鹏博士(600804)已经和解获赔,4.5万股民,还有多少没有上车! 药明康德再引关注,长跑型资产的配置价值仍清晰 史上最强nova正式发布:以“史上最强”实力,重塑新机价值标杆|华为nova 会计操纵曝光 贵州百灵多位高管独董被追责|贵州百灵 我国海上最大油田年产油气突破4000万吨 创历史新高|油田 持股10%!金达莱拟使用自有资金3000万元向中科鸿泰增资|中国科学技术大学 央行副行长邹澜:一次性信用修复政策为曾经失信的个人提供容错纠正机会|失信 年末银行揽储升温,存款冲量暗流再起|存款 酒价内参12月20日价格发布 市场整体上扬国窖1573领涨 品高股份荣获广东省卓越人工智能与机器人奖(XAIR奖)|人工智能 UQPAY 正式获批香港 MSO 牌照——加码布局亚太跨境支付网络 中南文化:2026年1月5日将召开2026年第一次临时股东会 向新而行|“两新”加力促内需 优步联手百度 将在英国伦敦开展无人驾驶出租车试运行 民族团结进步促进法草案二审 丰富维护国家象征和标志尊严相关内容 技术研发人员涨薪?比亚迪:情况属实|比亚迪