Application and energy saving of plate heat exchanger in data center

1, water cooling system
From 2005 to 2009, the Internet industry developed rapidly, and the demand for data services soared. Data centers with small scale and low power density had to bear a lot of IT equipment. At this time, the power density of the single cabinet has increased to 3~5kw, and the size of the data center has gradually increased. Medium-sized data centers with hundreds to thousands of cabinets have begun to appear. As the scale has grown, data center energy consumption has increased dramatically, and energy conservation issues have begun to receive attention.
The traditional air-cooled direct expansion system has lower energy efficiency than COP (Coefficient Of Performance). The COP in Beijing is about 2.5~3.0. The air-conditioning equipment consumes a lot of power and accounts for a high proportion of the overall power consumption of the data center. Moreover, with the expansion of installed capacity, the installation position of the air-cooled condenser reserved in the original data center building is seriously insufficient, and the noise disturbance problem is prominent, which restricts the expansion of the data center. At this time, the chilled water system widely used in office buildings began to be gradually applied to the data center refrigeration system. Since the COP of the chiller can reach 3.0~6.0, the large centrifugal chiller is even higher, and the chilled water system can greatly reduce the data. The center operates energy consumption.
The chilled water system is mainly composed of a chiller, a cooling tower, a chilled water pump, a cooling water pump, and a chilled water type air conditioner end. The system adopts centralized cold source, the cooling efficiency of the chiller is high, and the cooling tower is placed in a flexible position, which can effectively control the noise and benefit the aesthetic appearance of the building. After reaching a certain scale, it has more construction cost and maintenance cost than the direct evaporative system. Economic advantage.
Cooling system
The end of the air-conditioning system used in the chilled water system is a chilled water-type precision air conditioner, and its single cooling capacity can reach more than 150kw. The air supply mode and the previous air-cooled direct expansion system have not changed much, only the cooling medium in the end changes. The air conditioning equipment is still far away from the IT heat source, and mainly relies on the air-conditioning fan to deliver air to maintain the airflow organization.
 2, plate heat exchanger and water cooling system natural cooling
From 2010 to the present, with the development of data center cooling technology and people's further attention and pursuit of data center energy consumption, the concept of natural cooling has gradually been applied to the data center.
In the northern part of China, the outdoor temperature is lower in winter, and the water side natural cooling system is used. In winter, there is no need to open the mechanical refrigeration unit, and the cooling tower and the plate heat exchanger are used to “free” to obtain the cold source, thereby reducing the energy consumption of the data center. The water side natural cooling system is a set of plate heat exchangers and related switching valve groups above the original chilled water system. The chiller mechanical cooling is still used in high temperature weather, and the low temperature cooling water prepared by the cooling tower is used in the low temperature season. The high-temperature chilled water is exchanged for heat. In the transitional season, the lower-temperature cooling water and the higher-temperature chilled water are pre-cooled before entering the chiller, and the chiller load and running time can be reduced.
Principle of natural cooling system for water cooling system
 
The temperature of chilled water in traditional data centers is generally 7/12 °C. For example, in Beijing, natural cooling can be used 39% of the year. If the chilled water is raised to 10/15 °C, the natural cooling time will be extended to 46%. At the same time, due to the increase of evaporation temperature, the COP of the chiller can be increased by 10%. On the other hand, as the server withstands the increase in temperature, the chilled water temperature can be further increased, and the natural cooling time throughout the year will be further extended. At present, the domestic technology-leading data center has increased the chilled water temperature to 15/21 °C, and the natural cooling time can reach 70% or even longer.
2019/05/10 20:04:16 3705 Click

11月银行结售汇顺差157亿美元 跨境资金流动和外汇市场预期平稳|银行 迪士尼《阿凡达:火与烬》北美首映票房惨淡,仅收8800万美元 聚焦未来能源等四大前沿领域 上海交大闵行北校区创新功能规划发布 道通科技递表港交所 拟于港交所主板上市|港交所 日本10年期国债收益率上升7个基点至2.09% 国会搁置争议,医保问题成1月焦点 国仪量子IPO状态变更为已问询|IPO 智汇期现,共赢未来——2025年ETF与衍生品策略研讨会在上海成功举办 仙琚制药续聘张王伟为董秘:2024年薪酬96.81万 今年9月被监管警示 原信托监管标杆谢幕:邓智毅荣退! 昆仑信托总经理江昱洁:信托绝不是逃债避债的工具,也不是减免税负的工具 亚洲股市普涨 日元汇率走低 外交部:中方对日本首相官邸高官拥核言论感到震惊 扬帆中国茶饮大航海时代,奈雪的茶荣膺“2025国民影响力”荣誉 支付不用扫,碰一下就行!这项你正在用的功能,刚拿了国际大奖 美国发布先进空中交通战略 关税回调难解美国“咖啡之痛” 半导体板块持续走高,立昂微、珂玛科技双双涨停|半导体 枪击案一周后 悉尼邦迪海滩举行悼念遇难者活动 原油周报:原油阶段性企稳,地缘成为主要推手 盛视科技收购Aldebaran,改写全球人形机器人格局